UK AAIB AAIB-2007-N786UA · UK AAIB · Formal report

Boeing 777-222United Airlines Incorporated Aircraft Type and Model: Boeing 777-222

London Heathrow Airport · 2007-02-26·N786UA

Open this case in FlarePathSign inThe record below is free to read. An account opens the recorders, the photographs and the Analyst.
0
fatal
0
serious
Minor injury
highest injury
—
damage

What happened

AAIB synopsis, verbatim

Summary: The aircraft operator’s duty manager at Heathrow notified the Air Accidents Investigation Branch (AAIB) of the accident at 1140 hrs on 26 February 2007 and the investigation commenced the next day. The AAIB investigation team comprised: Mr K Conradi (Investigator-in-Charge) Mr N Dann (Operations) Mr S Hawkins (Engineering) Mr R James (Flight Recorders) A preliminary report on the initial findings from the accident was published in AAIB Special Bulletin S2-2007 on 17 April 2007. This formal report contains the final findings and Safety Recommendations from the investigation. The accident occurred during engine start after pushback from the stand. After the right generator came online an electrical failure occurred in the right main bus. The failure resulted in severe internal arcing and short circuits inside the two main power contactors of the right main bus. The heat generated during the failure resulted in the contactor casings becoming compromised, causing molten metal droplets to fall down onto the insulation blankets below. The insulation blankets ignited and a fire spread underneath a floor panel to the opposite electrical panel (P205), causing heat and fire damage to structure, cooling ducts and wiring. The flight crew responded to the bus failure and a burning smell by shutting down the right engine and taxiing to a nearby stand. The Airfield Fire Service attended the aircraft when it arrived on stand and entered the Main Equipment Centre where they discovered significant smoke but no fire. The passengers were evacuated uneventfully via steps. The investigation identified the following causal factors: An internal failure of the Right Generator Circuit Breaker or Right Bus Tie Breaker contactor on the P200 power panel inside the Main Equipment Centre resulted in severe internal arcing and short-circuits which melted the contactor casings. The root cause of contactor failure could not be determined. The open base of the P200 power panel allowed molten metal droplets from the failed contactors to drop down onto the insulation blankets and ignite them. The aircraft’s electrical protection system was not designed to detect and rapidly remove power from a contactor suffering from severe internal arcing and short-circuits. The contactors had internal design features that probably contributed to the uncontained failures.

Conclusion

the AAIB's conclusion, verbatim
Causal factors The following causal factors were identified: 1. An internal failure of the Right Generator Circuit Breaker or Right Bus Tie Breaker contactor on the P200 power panel inside the Main Equipment Centre resulted in severe internal arcing and short-circuits which melted the contactor casings. The root cause of contactor failure could not be determined. 2. The open base of the P200 power panel allowed molten metal droplets from the failed contactors to drop down onto the insulation blankets and ignite them. 3. The aircraft’s electrical protection system was not designed to detect and rapidly remove power from a contactor suffering from severe internal arcing and short-circuits. 4. The contactors had internal design features that probably contributed to the uncontained failures.

Safety recommendations

5 issuedwhat changed because of this accident
  • AAIB 2009-021issued

    Boeing Commercial Airplanes should consider implementing differential current fault protection of main power contactors when designing future electrical systems.

  • AAIB 2009-022issued

    ). The newly modified contactors address a number of the failings uncovered during the investigation. They do not necessarily fix the unknown root cause of the N786UA contactor failure, but the larger arc chute, improved heat resistant materials and additional internal insulation reduce the risk of a repeat failure from resulting in an uncontained contactor failure. The power panel cooling modification may also reduce the risk of a recurrence of the N786UA failure event, but analysis of the possible contactor failure causes revealed that excessive heat was not necessarily the initiating cause of failure. Therefore it is accepted that although beneficial, the cooling

  • AAIB 2009-023issued

    ) HEAT Contactor Breakdown Phase to Phase or Phase to Ground Short Assembly Error Reduced over-travel setting (plus normal erosion) Contamination during assembly Arc spray deposits Broken pigtail foil Conductive FOD Short of foil Support block dielectric breakdown Short-circuit Loose screws Excessive fault current Sustained parallel sources ‘Welded’ contact Phase to phase arcing Arcing at plunger to panel interface Arc chute degradation Movable contact pushrod failure ‘Heat set’ of plunger spring Sustained main contact arcing Insulating FOD on main contacts Increased contact resistance Degradation of insulating materials (epoxy flakes) Armature fouling Loss of over-travel loss of main contact force Softening of support block Displacement of threaded insert ‘Heat set’ of movable contact spring Contact chatter Loose junction Figure 53 Diagram listing possible causes of contactor failure

  • AAIB 2009-024issued

    The Federal Aviation Administration, in conjunction with the European Aviation Safety Agency, should mandate that all Boeing 777 aircraft be equipped, at the earliest opportunity, with a software update that will generate a caution message to alert flight crew of the presence of smoke in the Main Equipment Centre. The aircraft manufacturer responded to this Safety Recommendation by stating:

  • AAIB 2009-025issued

    The Federal Aviation Administration, in conjunction with the European Aviation Safety Agency, should mandate that all Boeing 777 aircraft be equipped, at the earliest opportunity, with a containment tray below the open base of the P100, P200 and P300 power